Ferroresonance and Transformer Connections
are related as such that the latter is a significant factor to the occurrence
of the former during loss of phase or open phase conditions. There are certain transformer
configurations that are more susceptible to ferroresonance. Generally, ferroresonance
phenomenon becomes highly probable if the primary windings of the three-phase
transformer are ungrounded.
Susceptible Transformer Connections
Susceptible Transformer Connections
Ferroresonance is more likely to
happen with transformer banks of certain connections, particularly when the
bank is energized or deenergized using single-pole switches at a location
remote from the transformer, or when a conductor or fuse at a relatively
distant location opens. The table below shows frequently employed three-phase
transformer connections, which are prone to ferroresonance.
Transformer Connections Susceptible to Ferroresonance (IEEE) |
The possibility of ferroresonance also
depends on the system and transformer electrical characteristics. Given a particular
transformer connection, the presence of phase-to-phase and/or phase-to-ground
capacitance of the lateral circuit and the transformer internal capacitance are
the main parameters that have the most effect on the establishment of
ferroresonance during loss of phase or open-phase conditions. The phenomenon
will happen only if the capacitances of the transformer and lateral circuit are
within a given range. The lower and upper bounds of this capacitance range are
established by the transformer size and design, as well as the primary voltage.
Typically, ferroresonance is more probable with smaller transformers in higher
primary voltage.
In other words, the chance of
occurrence is increased as:
·
Transformer
connection is one of those listed above
·
Transformer
size is reduced
·
Primary
voltage is increased
·
Lateral
length is increased
·
Lateral
conductor is underground shielded cable
Nonetheless, ferroresonance can occur
even if NOT all of the above-mentioned conditions are satisfied. For example, in
a 34.5 kV multigrounded neutral overhead system, ferroresonance with
overvoltages as high as 4-5 per unit has been recorded when energizing, even at
transformer terminals, ungrounded WYE-delta banks utilizing small single-phase
transformers. On the other hand, although not likely, ferroresonance can occur
for primary voltages below 12 kV when single-conductor shielded cable is used
to connect the single-pole fuses to the transformer.
Least Prone Transformer Connections
Three-Phase Transformer Bank Connections
indicated below are least susceptible to ferroresonance. This is because the
line-to-ground capacitance of the lateral line and transformer is bypassed by
the solid connection to ground. However, please take note of the term “least
prone” – meaning they can still be subjected to ferroresonance but at a lower
risk.
Ferroresonance-Free Transformer Connections |
For example, if YG–yg
transformer is supplied through open-wire circuits where phase-to-phase
capacitance exists, ferroresonance could occur whether or not the bank consists
of three single-phase units or is a triplex three-phase unit.
Fortunately,
the length of line required for ferroresonance under these conditions (over
three kilometers) is greater than that which normally exists between the
single-pole devices and the transformers. However, there should be caution if a
delta or ungrounded wye capacitor bank is installed between the single-pole
devices and transformer, since such condition leads to ferroresonance.
Otherwise,
the transformer connection with grounded WYE or grounded OPEN WYE primary is
considered free from ferroresonance.
Reference:
IEEE C57.105-1978. Guide for Application of
Transformer Connections in Three-Phase Distribution Systems
2 comments:
Thank you for this helpful stuff I got at your site. The stuff here is really good and keep up sharing. I will bookmark this page now and will be back soon to get more.
Facebook Development
Hi Angelina,
Thanks for the positive comments...
Post a Comment